How it works
3
min read

Technical specifications of a digital heat server

Find here the technical specifications of Northeast Flow's digital heat server.

Technical specifications of a digital heat serverTechnical specifications of a digital heat server

Physical dimensions

Northeast Flow digital heat server measures 800 x 420 x 420 mm. Its compact, standalone and stackable form ensures easy integration into a variety of settings where floor space might be limited.

Electrical & thermal specifications

Using 3-phase power, our digital heat server draws 15A per phase with a total electrical power input of 10350W.

Thermally, the server unit operates at flow rate of 16 liters per minute with a pressure drop of 65 kPa. With maximum inlet water temperature of 50°C the unit facilitates effective heat transfer. Heat capture efficiency of the unit is high and in suitable places 100% of the consumed energy can be reused.

Connections

In addition to electrical connection, the server unit is equipped with ½” pipe unions for water connections and ethernet connections enabling seamless integration.

Environmental

The digital heat server can operate in regular boiler room conditions at a maximum ambient temperature of 35°C.